Domain 1: Use status and diagnostic indicators to troubleshoot a PLC

Question 1

An HMI diagnostic screen shows both Home and Extended ON for a cylinder whose end positions are mutually exclusive. The cylinder is physically extended. A live connection to the correct PLC shows Home = 0 and Extended = 1, with no input forces. The PLC data update normally, but the HMI values have a last-update time six minutes old. This screen is read-only and has no control or safety function. The best initial response to the conflicting display is to:

Show answer & explanation

Correct answer: A - Investigate the HMI communication and data-update path before changing the PLC application.

Domain 2: Troubleshoot PLC inputs and outputs

Question 2

A carton diverter does not move although its PLC output command and channel LED are ON. The circuit is +24 V -> sourcing output -> valve coil -> supply 0 V. During an authorized test, a qualified technician measures 24.0 V from each coil terminal to supply 0 V, but 0.0 V directly across the coil. The coil remains connected, and there are no alternate feeds. Which fault best explains this pattern?

Show answer & explanation

Correct answer: B - An open return connection between the coil and supply 0 V.

Question 3

A three-wire proximity sensor was replaced during maintenance. Its indicator responds to the target, but the PLC input no longer turns ON. The replacement is an NPN sinking sensor; the removed unit was PNP sourcing. The PLC input is sinking-only, with its common connected to supply 0 V, and the other PNP sensors on that common still work. Supply voltage and pin assignments have been verified. Which repair matches the existing input circuitry?

Show answer & explanation

Correct answer: D - Fit a correctly rated PNP sourcing sensor and retain the existing common wiring.

Domain 3: Troubleshoot PLC power distribution system

Question 4

Loaded testing of a 24 V DC branch gives these readings: 24.0 V at the supply, 20.0 V across the load, 0.50 A through the branch, and 4.0 V directly across one feed connector. Other wiring losses are negligible. The load requires at least 21.6 V, and its disconnected supply cable reads 24.0 V with no load attached. Which assessment correctly combines the resistance calculation with the repair decision?

Show answer & explanation

Correct answer: B - 8.0 ohms at the connector; repair it and repeat the loaded-voltage test.

Domain 4: Troubleshoot a PLC processor

Question 5

After a software change, a Logix controller faults whenever an operator enters a recipe identifier that is not in the recipe table. The recorded major fault is a task-watchdog timeout. Code inspection finds a search loop that repeats until MatchFound becomes true, with no exit for an unmatched identifier. Which correction belongs in the application before further controlled testing?

Show answer & explanation

Correct answer: A - Add a finite search bound and an explicit path for an unmatched recipe.

Domain 5: Troubleshoot a PLC system with discrete I/O

Question 6

A technician is about to disconnect a valve line on a PLC-controlled pneumatic lift. The electrical disconnect and incoming air isolation valve are locked out. However, a fixture remains suspended by the cylinder, a cylinder-side gauge still reads 5.6 bar, and no mechanical restraint is installed. What must happen before the line is loosened?

Show answer & explanation

Correct answer: C - Restrain the load with approved supports, relieve trapped pressure, and verify the line is depressurized.

Question 7

A conveyor will not start automatically. The start-request input reaches the PLC, but the normal motor-output command stays OFF. During an authorized, guarded output-force test, the contactor picks up and the conveyor runs; removing the force stops it. No wiring or hardware was changed between these observations. What has this test established?

Show answer & explanation

Correct answer: C - The downstream output and motor path can operate; the normal command logic still needs investigation.

Domain 6: Program and operate a multi-step PLC sequence program

Question 8

Step 20 of an indexing sequence may advance only after ClampClosed has remained 1 continuously for 2.0 seconds while that step is active. A non-retentive ON-delay timer has a 2.0-second preset and resets when its enable is false; DN is its done bit. Each scan updates the timer before testing advance, using the same sampled Step and ClampClosed values. No other logic writes the timer. Select the conditions that enforce the dwell, even if closure is delayed or briefly lost.

Show answer & explanation

Correct answer: D - Enable: (Step = 20) AND ClampClosed. Advance: (Step = 20) AND DN.

Question 9

An automatic sequence may leave Idle only when a run request is present and an ordinary operator Stop circuit is healthy. Its normally closed contact produces StopHealthy = 1 when released and 0 when pressed or when the wire opens. Independent safeguards handle hazardous motion. In a Logix ladder rung, which placement of the StopHealthy test implements the required start permissive?

Show answer & explanation

Correct answer: B - XIC(StopHealthy), in series with the run request.

Domain 7: Troubleshoot a multi-step PLC sequence program

Question 10

A transfer sequence remains in Retract even after the cylinder reaches its home stop. The exit condition is Home AND NOT Extended. At that moment, Extended = 0 and raw input module 2, channel 3 = 1. The approved I/O list assigns the home sensor to that channel, but the online Home alias references module 2, channel 4, whose value is 0. There are no forces. Identify the correction that addresses the blocked transition.

Show answer & explanation

Correct answer: C - Correct the Home alias to reference module 2, channel 3, as documented.